Dual Winding Oil Immersed Distribution Transformer with On-Load Tap Changer
As a reliable manufacturer in China, Ceho provides high quality and advanced Dual Winding Oil Immersed Distribution Transformer with On-Load Tap Changer. The product is a powerful and universal medium-voltage distribution solution that can provide real-time voltage regulation without interrupting the power supply.
Ceho Dual Winding Oil Immersed Distribution Transformer with On-Load Tap Changer has durable quality and advanced technology. Applied in urban and industrial distribution networks; Substations that require stable voltage; Integration of renewable energy (solar energy/wind energy) Areas such as load centers with fluctuating demand.
Feature
Description
Winding Configuration
Dual (two) windings – typically HV and LV – with no autotransformer connection, allowing galvanic isolation and flexible voltage ratios .
Voltage Regulation
On-load tap changer allows ±8 × 1.25% or wider regulation range on HV side, enabling automatic voltage control under load .
Tap Changer Design
Vacuum-type OLTC housed in a separate oil-filled compartment, isolated from the main tank oil to prevent contamination and simplify maintenance .
Cooling Method
Standard ONAN (Oil Natural Air Natural); ONAF or OFAF available for higher ratings or overload conditions .
Vector Group
Common groups include Dyn11, Yzn11, or YNd11, depending on grounding and system requirements .
Construction
Core-type design with copper windings, corrugated steel tank, and hermetically sealed structure for durability and reduced maintenance .
Control & Monitoring
Supports local and remote electrical operation, manual emergency operation, and automatic voltage regulation with voltage relay and overcurrent lockout .
10kV Double-winding Power Transformers with On-load Tap-changer
Rated
Capacity
Voltage ratio
(KV)
Vector
Group
No-load
Loss
No-load
Current
Full-load
Loss
Impedance
(kVA)
HV
Tapping
Range
LV
(kW)
(%)
(kW)
(%)
6300
110
121
±8×
1.25%
6.3
6.6
10.5
11
YNd11
10
0.6
36
10.5
8000
12
0.6
45
10000
14.2
0.55
53
12500
16.8
0.55
63
16000
20.2
0.5
77
20000
24
0.5
93
25000
28.4
0.45
110
31500
33.8
0.45
133
40000
40.4
0.4
156
50000
47.8
0.4
194
63000
56.8
0.35
234
75000
63.4
0.35
278
90000
73.1
0.3
320
120000
91.2
0.3
397
Maintenance and Safety
Dual Winding Oil Immersed Distribution Transformer with On-Load Tap Changer is equipped with its own Buchholtz relay, oil level gauge and breather to ensure independent monitoring and protection. Temperature monitoring in the OLTC room is of vital importance. An increase in temperature may indicate contact wear or oil degradation.
It is recommended to conduct contact checks and oil tests every 2 to 3 years to prevent coking and ensure reliable operation
For inquiries about power transformer, box-type substation, switchgear or price list, please leave your email to us and we will be in touch within 24 hours.