Q1: What are the uses of current transformers?

A1: Current transformers convert large currents into small currents in a certain proportion, providing currents for various instruments and relay protection, and isolating secondary systems from high voltages. It not only ensures the safety of personnel and equipment, but also simplifies and standardizes the manufacturing of instruments and relays, improving economic efficiency.


Q2: Why is it not allowed for current transformers to operate under overload for a long time?

A2: Long term overload operation of current transformers can increase errors and result in incorrect meter readings. In addition, due to the increase of primary and secondary currents, the iron core and winding will overheat, the insulation will age quickly, and even damage the current transformer.


Q3: What causes abnormal sound in the operating current transformer?

A3: Overload of current transformers, open circuit on the secondary side, and discharge due to internal insulation damage can all cause abnormal sound. In addition, internal corona caused by uneven coating of semiconductor paint and loose clamping screws can also cause significant noise in current transformers.


Q4: Why is there no fuse installed on the primary side of 110kV and above voltage transformers?

A4: Because the structure of 110kV and above voltage transformers adopts a single-phase cascade type with high insulation strength, and because the 110kV system is a neutral point directly grounded system, each phase of the voltage transformer cannot withstand line voltage operation for a long time, so no fuse is installed on the primary side.


Q5: Why is it not allowed to replace the primary fuse of a voltage transformer with a regular fuse after it has blown?

A5: Taking a 10kV voltage transformer as an example, the rated current of the primary side fuse is 0.5A. Fuses filled with quartz sand have good arc extinguishing performance and large breaking capacity, while also limiting short-circuit current. However, ordinary fuses cannot meet the requirements for breaking capacity.


Q6: What fault can cause the primary and secondary fuses of voltage transformers of 35kV and below to melt?

A6: Internal faults of voltage transformers, including phase to phase short circuits and winding insulation damage, as well as short circuit faults and resonant over voltages in the connection wires between the voltage transformer outlet and the power grid, can cause the primary side fuse to melt. Short circuit faults in the secondary circuit can cause the secondary side fuse of the voltage transformer to melt.


Q7: What issues should be noted when disabling voltage transformers?

A7:

(1) Do not cause the protective automatic device to lose voltage.

(2) Voltage switching is necessary.

(3) To prevent reverse charging, remove the secondary lead wire (including capacitors).

(4) After all secondary loads are disconnected, disconnect the primary power supply of the transformer


Q8: What are the phenomena and hazards of secondary short circuit in voltage transformers? Why?

A8:

A secondary short circuit in a voltage transformer can cause a large short-circuit current in the secondary coil, burn the winding of the voltage transformer, and even cause primary and secondary breakdown, resulting in protective misoperation and no indication from the instrument. Because the impedance of the voltage transformer itself is very small, and the primary side is a constant voltage power supply, if there is a secondary short circuit, a large short-circuit current will be generated in the secondary winding under the action of the constant voltage power supply, which will burn the transformer, cause insulation damage, and lead to primary and secondary breakdown. Losing the voltage transformer will cause misoperation of distance protection and voltage related protection, resulting in no indication from the instrument and affecting system safety. Therefore, the voltage transformer cannot be short circuited in the secondary.


Q9: What is the impact of voltage transformer faults on relay protection?

A9:

Common faults in the secondary circuit of voltage transformers include: blown fuses, poor contact of auxiliary contacts of isolation switches, loose secondary wiring, etc. The result of a fault is a decrease or cancellation of the voltage of the relay protection device. For protection relays that reflect the voltage decrease and protection devices that reflect the phase relationship between voltage and current, such as directional protection, impedance relays, etc., it may cause misoperation and refusal to operate.


Q10: What protections should be stopped when the voltage circuit breaks or the voltage transformer malfunctions?

A10:

Should stop protection: current and voltage protection controlled by directional components; Low voltage or composite voltage lockout over current protection; Current balance protection; Distance protection; Horizontal differential direction protection; Protection against tripping due to a decrease in reaction voltage; Low frequency protection. Because the above protections are all related to voltage changes, in order to prevent voltage circuit disconnection or voltage transformer failure, the voltage related protections should be immediately disconnected.