I. What is the GT-12?
The GT-12 Smart Solid-Insulated Switchgear is a 12 kV (extendable to 24 kV), 50 Hz indoor AC metal-enclosed solid-insulated switchgear. It integrates all high-voltage live parts—including busbars, isolating switches, vacuum arc extinguishers, and connection terminals—into a single modified epoxy resin insulation module through the APG (Automatic Pressure Gelation) process. The outer surface is coated with a grounding shielding layer, achieving true full insulation, full sealing, full shielding, and touch-safe operation.
To put it simply: the solid insulation provides insulation, while the vacuum extinguishes the arc. Insulation no longer relies on gas pressure, so its performance is decoupled from ambient atmospheric pressure—this is the physical foundation that enables it to operate in high-altitude and extremely cold environments.
Each unit is structurally divided into three layers that do not interfere with one another:
|
Layer |
Content |
Value |
|
Smart Meter Room |
Microprocessor-based protection / Smart controllers, measurement and control terminals, wireless communication modules |
On-site intelligence; upgrades possible without modifying the primary circuit |
|
Operating Mechanism Layer |
Integrated spring-storage mechanism; electric operation available as an option |
Manual and electric operation share the same architecture; natively compatible with distribution network automation |
|
Primary Circuit Layer |
APG cast resin-encapsulated busbars + encapsulated busbars + dedicated plug-in connectors |
Fully sealed and maintenance-free; physical isolation between phases |
II. Three Types of Modules, Flexible Cabinet Configuration
The GT-12 features a modular architecture consisting of V, C, and F modules. Each cabinet can be used independently or combined in any configuration according to the main wiring diagram:
Selection Guidelines:
Generally, use 630A for incoming lines, busbar breakers, and standard feeder circuits; for transformer feeders, high-capacity feeder circuits, and critical load circuits, 1250A / 25kA is recommended. Three-position isolation plus grounding provides a visible and reliable break, offering a sense of security on the maintenance side that all-gas switchgear cannot provide.
III. Main Technical Parameters (12 kV Rating)
| Item | Unit | V Unit | C Unit | F Unit |
| Rated Voltage | kV | 12 | 12 | 12 |
| Rated Current | A | 630 | 630 | 630 (fuse ≤ 125 A) |
| Rated Short-Circuit Breaking Current | kA | 25 | — | 31.5 (fuse interruption) |
| Rated Short-Time Withstand Current / Time | kA / s | 25 / 4 | 25 / 4 | — |
| Rated Peak Withstand Current | kA | 63 | 63 | — |
| Rated Short-Circuit Closing Current | kA | 63 | 63 | 80 |
| Rated Transfer Breaking Current | A | — | — | 3150 |
| Power-Frequency Withstand Voltage (Phase-to-Phase / Phase-to-Ground · Break) | kV / 1 min | 42 · 48 | 42 · 48 | 42 · 48 |
| Lightning Impulse Withstand Voltage (Phase-to-Phase / Phase-to-Ground · Break) | kV | 75 · 85 | 75 · 85 | 75 · 85 |
| Main-circuit resistance | μΩ | ≤140 | ≤140 | ≤700 |
| Mechanical life | cycles | 10,000 | 10,000 | 10,000 |
| Partial discharge in solid insulation (1.2Ur) | pC | ≤5 | ≤5 | ≤5 |
| Total Cabinet Partial Discharge (1.2Ur) | pC | ≤20 | ≤20 | ≤20 |
| Protection Rating | — | Live Parts IP67 / Cabinet Enclosure IP4X | Same as above | Same as above |
| Dimensions (Single Unit, W × D × H) | mm | 400(500) × 830 × 1650 | Same as above | Same as above |
Applicable Standards: GB/T 3906-2020, GB/T 11022, GB 1984, GB 3804, GB 16926, GB/T 15166.2, GB/T 7354, IEC 62271-200, IEC 62271-1, and complies with the relevant requirements of Q/GDW 730 “Technical Specifications for 12 kV Solid-Insulated Ring Main Units.” Specific delivery parameters shall be subject to the technical agreement in the contract and the corresponding type test reports.
Operating Environment
Ambient Temperature: −45°C to +45°C (No concerns regarding low-temperature liquefaction of SF₆)
Altitude: ≤ 4,000 m; insulation performance does not degrade with atmospheric pressure, and no insulation derating is required for high-altitude conditions
Humidity: Daily average relative humidity ≤ 95%; monthly average ≤ 90%
Seismic Resistance: 8 degrees | Condensation, contamination, and salt fog conditions verified in accordance with GB/T 3906, Appendix E
IV. Where It Is Best Suited
Top Recommendations
Situations Requiring Careful Evaluation
Let’s be honest about the shortcomings of the solid-insulation approach: the heat dissipation pathways and partial discharge control in resin-insulated components are extremely sensitive to formulation and casting processes; once the insulation component itself is damaged, replacing it on-site is not as convenient as swapping out a module in a gas-insulated cabinet—typically, the entire encapsulated assembly must be replaced. Therefore:
When selecting a solid-insulation switchgear, don’t just compare quotes for the cabinet itself; consider three key factors: the grading of the insulating material fillers and APG process capabilities; the coverage of factory acceptance testing, including X-ray inspection, partial discharge testing, lightning impulse testing, and high-low temperature cycling; and valid type test reports that correspond exactly to the model you are procuring (GB/T 3906-2020 stipulates that type test reports are valid for 8 years; if expired, difference tests must be conducted).
FAQ
Q1: Are solid-insulated switchgear units more expensive than gas-insulated switchgear units?
The initial investment per unit is generally on par with that of gas-insulated switchgear units of the same specifications, though some high-end, intelligent models may be slightly more expensive. However, when factoring in 15 years of leak detection, gas replenishment, gas recovery, power outage windows, and labor costs, the total life-cycle cost is typically lower—since it eliminates the entire “gas management” category.
Q2: How are faulty insulation components repaired?
Peripheral components such as switches, fuse tubes, bushings, and mechanisms can be replaced individually; however, the cast-sealed primary circuit assembly is typically replaced as a whole unit. This is why the stringency of factory partial discharge testing and X-ray inspection directly determines whether you’ll need to perform this replacement ten years down the line.
Q3: Can this directly replace my current SF₆ switchgear?
In most cases, yes. The width of the GT-12 unit is comparable to that of mainstream gas-insulated switchgear. Focus on verifying three key points: the clear operating distance in front of the cabinet, the feed-in height and phase sequence in the cable compartment, and the direction of busbar expansion. Before placing an order, send the floor plan of the original cabinet and the cable inventory list to our technical team for a replacement verification—it’s much cheaper than making adjustments after installation.
Q4: Are 24 kV and 40.5 kV versions available?
The 12 kV model is the flagship of the platform; the 24 kV version is already available as a series on the same platform. The 40.5 kV solid-insulated solution can be customized for specific projects, but insulation compatibility and type test coverage must be confirmed separately.
Q5: Will intelligent features compromise reliability?
No, provided that the intelligent layer is physically isolated from the primary layer. The GT-12 features a dedicated instrument room; a failure in the intelligent unit only affects “visibility” and does not affect “trip capability”—protection trip circuits retain hard-wired direct-trip paths, ensuring that basic protection functions remain intact even in the event of network outages or system crashes.