I. Immediate Actions (Safety First)
1.De-energize from the upstream breaker. Never operate close to the transformer. If protection has tripped, do NOT reset/reclose repeatedly.
2.Isolate & secure. Open disconnectors, hang “DO NOT OPERATE” tags, set up a exclusion zone. Keep clear, especially in wet conditions.
3.Evacuate if you see: heavy smoke, burning smell, oil spray/leak, loud banging/arcing, bulging tank, rapid temperature rise. Contact fire services and utility personnel.
4.Fire on oil-filled units: Never use water on live equipment. After confirmed de-energization, use CO₂ / dry powder / fixed fire-suppression system.
II. Troubleshooting (Qualified Personnel Only)
| Check | What to Look For | Purpose |
| Protection relays | Differential, overcurrent, Buchholz, pressure relief | Internal fault vs. external downstream short |
| Visual inspection | Bushings, leads, oil level/color, leaks, rupture disc | Locate flashover / overheating |
| Oil tests (oil-filled) | Dielectric strength, moisture, DGA (dissolved gas) | Detect internal arcing / overheating |
| Electrical tests | Winding resistance, turns ratio, insulation, short-circuit impedance | Find winding deformation or turn-to-turn fault |
| Downstream circuit | Cables, busway, motors, LV switchgear | Most “transformer shorts” originate on the load side |
Quick Diagnosis
III. Repair or Replace?
IV. Never Do These
X Force multiple reclose attempts
X Restore load without insulation tests
X Use water on an energized oil-fire
X Reset relays without finding the root cause
X Treat oil filtering as a fix for internal faults
V. Prevention Checklist